Add:No. 508 Ganglong Road, Economic Development Zone, Yangzhong City, Jiangsu Province (212213 )
    Tel: 0511-88219009
    E-mail:sales@jsyineng.com

Blokset low-voltage switchgear

Publisher:Yineng group Release time:2018/12/29 10:20:52 Click on the:1387 Shut down






  • The Blokset system is designed to provide a high level of reliability and safety, thus reinforcing the protection of life and property.

    Blokset offers all the essential guarantees:

    compliance with international standards, notably IEC 60439-1, IEC 60529 and IEC 60947

    compliance with local standards, thus meeting local legal and technical requirements

    a system implementing and tested with Schneider Electric switchgear components to ensure optimum operation.



  • General data

    Application

    Power distribution

    Motor control

    IS(Operation and maintenance index)

    211 to 333

    Reference standard

    IEC60439-1

    IEC60529

    IEC61439-1&2

    IEC61641

    GB7251.1

    Climate tolerance

    Damp heat tolerance

    IEC60068-2-30

    Dry heat tolerance

    IEC60068-2-2

    Low temperature tolerance

    IEC60068-2-1

    Smoke tolerance

    IEC60068-2-11

    Installation Location

    Indoor

    Environment

    Class 2

    Mechanical data

    Cable inlet and outlet

    Top/bottom

    Wiring

    Front/Back

    Protection level

    IP20-54

    Isolated form

    2b/3b/4a/4b

    Link form

    FFF/WWW

    Dimension

    Height

    2200

    Width

    500/600/700/800/900/1000/1100/1200/1300

    Depth

    400/600/1000

    Average weight per unit

    650kg

    Enclosure

    Epoxy resin powder coating>50μ

    Frame

    Galvanized

    Color of enclosure

    RAL9002/RAL7016

    Electrical data

    Rated insulation voltage

    1000V

    Rated operating voltage

    400/690V AC

    Rated frequency

    50/60HZ

    Rated pulse voltage

    12KV

    Rated auxiliary circuit voltage

    230V AC max

    Overvoltage level

    Pollution level

    3

    Horizontal busbar rating

    Up to 7000A

    Vertical busbar rating

    Up to 3200A

    Horizontal busbar rating

    Rated short-time withstand current

    30/50/85/100KA

    Rated peak withstand current

    63/105/187/220KA

    Vertical busbar rating

    Rated short-time withstand current

    30/50/85KA

    Rated peak withstand current

    63/105/187KA

    Internal combustion arc personal protection IEC61641

    85KA 0.4s

    Grounding system

    TT-IT-TNS-TNC

    Maximum inlet and outlet switch

    6300A

    Maximum motor capacity

    250kw